Datasheet

Recovery time 500ms
Voltage
SIL Claim Limit (subsystem) / acc. to EN 62061 3
Surge voltage resistance / between contacts of the
relay operating mechanism
4kV
Switching capacity
Switching capacity voltage / of the contacts
● as NC contact / at DC-13
24V
● as NO contact / at DC-13
24V
Switching capacity current / of the contacts
● as NC contact / at AC-15
2A
● as NC contact / at DC-13
4A
● as NO contact / at AC-15
3A
● as NO contact / at DC-13
4A
● as CO contact / at AC-1
5A
Dissipation
Power loss [V∙A]
● of magnet coil / in relay operating mechanism
3.5V·A
● of the contact / in relay operating mechanism
0.8V·A
Main circuit
Operating frequency / rated value 50Hz
Control current
Type of voltage / of the control supply voltage AC
Control voltage / at connecting terminal Y1 / at
AC/DC
24V
Control supply voltage
● at AC / rated value
230V
● at AC / at 50 Hz / rated value / minimum
184V
● at AC / at 50 Hz / rated value / maximum
253V
● at AC / at 60 Hz / rated value / minimum
184V
● at AC / at 60 Hz / rated value / maximum
253V
Control current / at connecting terminal Y1 / at DC 45mA
Operating range factor / of control voltage_2 1.1
Suitability
Suitability for use
● safety switch
Yes
● magnetically operated switch monitoring
No
● proximity switch monitoring
No
● EMERGENCY-OFF circuit monitoring
Yes
● opto-electronic protection device monitoring
No
5TT5200 Subject to change without notice
Page 2/
4
12/13/2018 © Copyright Siemens