Data Sheet
Data sheet 5SV5342-6KL
Residual current operated circuit breaker, 4-pole, type A, In: 25 A, 30
mA, Un AC: 400 V, N left
Model
Product brand name SENTRON
Product designation RCCB
Design of the product Instantaneous
Product variations N left
General technical data
Number of poles 4
Size of installation devices / acc. to DIN 43880 1
Protection against electrical shock Finger and back-of-hand safe
Short-circuit current rating 10kA
circuit-breaker / Design 5SV5
Mechanical service life (switching cycles) / typical 10000
Switching function / short-term delayed No
Overvoltage category III
Supply voltage
Current / at AC / rated value 25A
● Supply voltage / at AC / rated value
400 V
● Supply voltage / for testing equipment /
minimum
195V
● rated value
50 Hz
Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Switching capacity
Switching capacity current / according to IEC 61008-
1 / rated value
0.8kA
Dissipation
Power loss [W] / for rated value of the current / at AC
/ in hot operating state / per pole
1.3W
Current
Tripping residual current / rated value 30mA
Tripping residual / rated value / derated current
● at 40 Cel
25A
● at 45 Cel
25A
5SV5342-6KL Subject to change without notice
Page 1/
3
09/13/2019 © Copyright Siemens