Datasheet

Protection class
Protection class IP IP20, with connected conductors
Energy limiting class 3
Switching capacity
Switching capacity current
● acc. to EN 60898 / Rated value
kA 6
● acc. to IEC 60947-2 / Rated value
kA 6
Dissipation
Active power loss
● for rated value of the current / at AC / in hot
operating state / per pole
W 1.2
Electricity
rated current In / IEC, DIN/VDE / at 40 Cel A 9.51662
Current / at AC / Rated value A 10
Main circuit
Operating voltage
● minimum
V 24
● at DC / Rated value / maximum
V 60
● with multi-phase operation / at AC / maximum
V 440
Product details
Product feature / Touch protection Yes
Product property
● halogen-free
Yes
● sealable
Yes
● silicon-free
Yes
Product expansion / can be installed / supplementary
devices
Yes
Product function
Product function / neutral conductor switching No
Number
Number of test cycles / for environmental testing /
acc. to IEC 60068-2-30
6
Connections
Connectable conductor cross-section / stranded
● minimum
mm² 0.75
● maximum
mm² 35
Connectable conductor cross-section
● solid
— minimum
mm² 0.75
5SL6310-7 Changes preserved