Data Sheet

Shock acceleration 30gn
Vibrational acceleration / at 5 Hz ... 500 Hz / limited
to 2,5 h / per axis
5gn
Ambient temperature / during operation -40°C...80°C
Ambient temperature / during storage and transport -40°C...80°C
Relative humidity / during operation 5%...95%
Installation altitude / at height above sea level /
maximum
2000m
Width 25.4mm
Height 90mm
Depth 71.5mm
Net weight 200g
Electrical data
Type of distribution system TT, TN-S
Operating voltage 240V AC
Operating voltage 230V
Continuous operating voltage
● maximum
350V
● between N and PE
264V
● between L and (PE)N
350V
Load current 40 A
Protective conductor current 1µA (255VAC)
Discharge current
● at (8/20) µs
20kA
● 1 phase / at (8/20) µs
40kA
Follow current extinguishing capability
● between N and PE
100 A (264 V a.c.)
Short-circuit rating (SCCR) / at 264 V 25kA
Protection level
● maximum
1.5kV
● between N and L
1.4kV
● between PE and N and/or L
1.5kV
Residual voltage
● between L and (PE)N
— at rated value of discharge current /
maximum
1.5kV
— at 10 kA / maximum
1.3kV
— at 5 kA / maximum
1.2kV
— at 4 kA maximum
1.1kV
— at 2 kA maximum
1kV
● between N and PE
— at rated value of discharge current /
maximum
0.5kV
5SD7422-0 Subject to change without notice
Page 2/
5
04/12/2019 © Copyright Siemens