Installation Instructions

Installation Instructions
Document No. 129-496
September 26, 2016
Ball Valve Bracket Kit
Item No.129-496, Rev. FA Siemens Industry, Inc.
Product Description
The Ball Valve Bracket Kit contains the parts necessary
to install an OpenAir® GDE/GLB Series non-spring
return actuator or OpenAir GMA and GQD Series
spring return actuator to a 599 Series two-way or three-
way ball valve.
The actuator is held in place by securing it to the
bracket shaft. The bracket shaft is held in place when
the bracket is properly screwed to the valve body.
Contents
Part Description
Qty
6/32-inch × 3/4-inch screw for handle
1
Ball valve handle
1
Bracket shaft
1
Bracket screws: M4 × 0.7 × 50 mm
2
Bracket screws: M4 × 0.7 × 53 mm
(For valves with yellow plate on top)
2
Bracket
1
Product Number
599-10078
Required Tools
No. 2 Phillips screwdriver
10 mm socket wrench for OpenAir GMA
actuator installation
4 mm hex key for OpenAir GDE/GLB actuator
installation
3 mm hex key for OpenAir GQD actuator
installation
Expected Installation Time
20 Minutes
Installation
Ensure that the ball valve is in the fully open position
with the valve stem in the orientation shown in Figure 1
and Figure 2.
Figure 1. Two-way Configuration.
Figure 2. Three-way Configuration.