Data Sheet for Product
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions
Document Number 155-717
September 25, 2018
Siemens Industry, Inc. Page 7
Mounting and
Installation
The vertical position is the recommended position for mounting and the only position for
NEMA Type 3R rating with the Weather Shield. Acceptable mounting positions are shown
in Figure 10.
Figure 10. Acceptable Mounting Positions.
Allow four inches (100 mm) around the sides and back of the actuator and eight inches
(200 mm) above and to the front of the actuator.
See dimensions in Figure 23, Figure 24, Figure 25, and Figure 26.
Detailed installation instructions for field mounting are shipped with the actuator.
CAUTION:
When removing the knockout do not damage the circuit board. Use
the top knockout position, if possible.
Start-up
Check the wiring for proper connections.
NOTE: The valve body assembly determines the complete assembly action.
Spring Return
Function
All SKB/C/D62UA actuators are factory-fitted with a spring-return function. If the control
signal or power supply fails, the actuator will return to the 0% stroke position (stem fully
retracted).
Override Control
The override control input (Z) has three modes of operation:
NOTE: The Z-modes have a "direct acting" factory setting.