Install Instructions

Document No. 129-215
Installation Instructions
September 29, 2009
Siemens Industry, Inc. Page 7 of 9
Installation, Continued
SKD Actuators
Tools
5 mm hex wrench
CAUTION:
Do not damage or scratch the polished
surface of the valve stem.
Removing the actuator
1. Turn off the power to the actuator.
2. Rotate the manual override knob three turns.
See Figure 16.
EA0482R1
5 mm
ACTUATOR
YOKENUT (2)
STEM
RETAINER
SCREWS
MANUAL
OVERIDE
KNOB
3x360
«MAN«MAN
«
Figure 16. SKD Actuator.
3. Use a 5 mm hex wrench to loosen the stem
retainer screws.
4. Lower the valve stem.
5. Use a 5 mm hex wrench to loosen the yoke
nuts.
6. Remove the actuator from the valve, being
careful not to damage the valve stem.
7. Return to the instructions for Removing the
packing cartridge.
Assembling the actuator to the valve
1. Place the actuator onto the valve bonnet. Finger
tighten the yoke nuts.
2. Raise the valve stem to meet the stem retainer.
3. Hold the stem retainer in place as you tighten it
around the valve stem. See Figure 17.
EA0384R1
5 mm
Figure 17. Fastening the Valve Stem in the Stem
Retainer.
4. Hold the actuator in place as you fasten the
yoke nuts with a 5 mm hex wrench.
5. Rotate the manual override knob until the red
tab indicates Automatic mode.
SQX Actuators
Tools
5 mm hex wrench
CAUTION:
Do not damage or scratch the polished
surface of the valve stem.
Removing the actuator
1. Turn off the power to the actuator.
2. Rotate the manual override knob one turn.
3. Use a 5 mm hex wrench to loosen the stem
retainer screws. See Figure 18.
ACTUATOR
YOKE
LOCK SCREW
MANUAL
OVERRIDE
KNOB
STEM
RETAINER
SCREWS (2)
STEM
RETAINER
STEM
POSITION
INDICATOR
YOKE
SCREW
(2)
EA0398R1
Figure 18. SQX Actuator.