Table 3. Maximum Water Capacity - U.S. Gallons per Minute.
Valve
Size
Pressure Differential - psi
inches
Cv\1
2 3 4 5 6 8 10 15 20 25 30 40 50 60 75
1/2
0.4 0.6 0.7 0.8 0.9 1.0 1.1 1.3 1.5 1.8 2.0 2.2 2.5 2.8 3.1 3.5
0.63
0.9 1.1 1.3 1.4 1.5 1.8 2.0 2.4 2.8 3.2 3.5 4.0 4.5 4.9 5.5
1.0 1.4 1.7 2.0 2.2 2.5 2.8 3.2 3.9 4.5 5.0 5.5 6.3 7.1 7.8 8.7
1.6 2.3 2.8 3.2 3.6 3.9 4.5 5.1 6.2 7.2 8.0 8.8 10.1 11.3 12.4 13.9
2.5 3.5 4.3 5.0 5.6 6.1 7.1 7.9 9.7 11.2 12.5 13.7 15.8 17.7 19.4 22
4 5.7 7 8.0 8.9 10 11.3 12.6 15.5 17.9 20.0 21.9 25 28 31 35
3/4 6.3 8.9 10.9 12.6 14.1 15.4 17.8 20 24 28 32 35 40 45 49 55
1 10 14.1 17.3 20 22 24 28 32 39 45 50 55 63 71 77 87
Table 4. Maximum Water Capacity - Cubic Meters per Hour (m
3
/hr).
Valve
Size
Pressure Differential - kPa
inch
(mm)
1 10 20 30 40 50 60 80
Kvs/
100
150 200 300 400 500
15
0.03 0.11 0.15 0.19 0.22 0.24 0.26 0.30 0.34 0.42 0.48 0.59 0.68 0.76
0.05 0.17 0.24 0.30 0.34 0.38 0.42 0.48 0.54 0.66 0.76 0.94 1.08 1.21
0.09 0.27 0.38 0.47 0.54 0.60 0.66 0.76 0.85 1.0 1.2 1.5 1.7 1.9
0.14 0.43 0.61 0.75 0.87 0.97 1.06 1.23 1.37 1.7 1.9 2.4 2.7 3.1
0.21 0.68 0.96 1.17 1.35 1.51 1.66 1.91 2.15 2.6 3.0 3.7 4.3 4.8
0.34 1.1 1.5 1.9 2.2 2.4 2.7 3.1 3.4 4.2 4.9 6.0 6.9 7.7
20 0.54 1.7 2.4 3.0 3.4 3.8 4.2 4.9 5.4 6.7 7.7 9.4 10.9 12.1
25 0.86 2.7 3.8 4.7 5.4 6.1 6.7 7.7 8.6 10.5 12.2 14.9 17.2 19.2