Brochure

7
Damper Actuator Cross Reference Wiring Diagrams
Replace failed or end of life damper actuators easily with Siemens OpenAir® damper actuators. Siemens offers a full
range of indirect mounting kits, as the examples at left show. Wiring cross reference tables shown below (displaying
wire color and number) are available in all Siemens OpenAir damper actuator installation instruction documents.
Go online to www.usa.siemens.com/damperactuatorwiringxref to download the complete Damper Actuator wiring
cross reference guide.
Modulating Control
(0 to 10 Vdc)
Siemens
GCA Series
Belimo
AFB Series
Honeywell
MS7520 Series
Johnson
M9220 Series
Function Color Number Color Number Color Number Color Number
Supply 24V Red 1 Red 2 Red 1 Red 2
Common Black 2 Black 1 Black 2 Black 1
0(2) to 10 Vdc Input Gray 8 White 3 White 3 Gray 3
0(2) to 10 Vdc Feedback Pink 9 Orange 5 Blue 5 Orange 4
Modulating Control
(2 to 10 Vdc)
Siemens
GQD Series
Belimo
TF Series
Honeywell
MS7503 Series
Johnson
M9203 Series
Function Color Number Color Number Terminal Only Number Color Number
Supply 24V Red 1 Red 2 1 Red 2
Common Black 2 Black 1 2 Black 1
2 to 10 Vdc Input Gray 8 White 3 3 Gray 3
2 to 10 Vdc Feedback Pink 9 Orange 5 5 Orange 4
Floating Control
Siemens
GDE Series
GLB Series
Belimo
LMB Series
NMB Series
Honeywell
MN6105 Series
MN6110 Series*
Johnson
M9104 Series
M9109 Series*
Function Color Number Color Number Color Number Color Number
Common Red 1 Black 1 Black 2 Black 1
24V CW Violet 6 Red 2 Red 3 Red 2
24V CCW Orange 7 White 3 White 4 Orange 3
Note: MN6110 Series and M9109 Series is not available precabled.
2-Position Control
(24 Vac/Vdc)
Siemens
GMA Series
Belimo
LF Series
NF Series
Honeywell
MS8105 Series
Johnson
M9208 Series
Function Color Number Color Number Color Number Color Number
Supply 24V Red 1 Red 2 Red 1 Red 2
Common Black 2 Black 1 Black 2 Black 1
Simplify installation with OpenAir
®
damper actuators