Installation Instructions
Table Of Contents
Hardware Map – VAV AHU
Termination
Set
Parameter Set in Element Name I/O Type Factory I/O Setting
StatTemp statTemp SPACE_TEMP
StatSetpt statSetpt
TEMP
IN_UNUSED
StatOvrd statOvrd DI STAT_SWITCH_DI
In1 in1 DISCH_TEMP
In2 in2
DI, TEMP
RETRN_TEMP
In3 in3 DUCT_PRESS
In4 in4 FAN_STATUS_DI
In5 in5 LOW_TEMP_DI
In6
inputs
in6
DI, PCT, TEMP
HI_PRESS_DI
OutA1 outA1 SUP_FAN_CAP_AO
OutA2 outA2
OA_DMPR_AO
OutA3 outA3
AO
HEAT_COIL_AO
OutD1 outD1 SUP_FAN_DO
OutD2 outD2
OA_DAMPER_2POS_DO
OutD3 outD3
DX_STAGE1_DO
OutD4 outD4
DX_STAGE2_DO
OutD5 outD5
DX_STAGE3_DO
OutD6 outD6
DX_STAGE4_DO
OutD7 outD7
HEAT_STAGE1_DO
OutD8
outputs
outD8
DO, FLT_MTR
HEAT_STAGE2_DO
Table 1. Hardware Map
Page 6 of 11
Document No. 588-150