Data Sheet for Product

Document No. 588-154 Page 27 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Sets up the limits for the value read from the
space temperature setpoint slide.*
minTemp 66.2°F
(19.0°C)
The minimum value that is accepted from the
space temperature setpoint slide*.
50.0 to 95.0°F
(10.00 to 35.00°C)
Type: SNVT_temp_p
tempSP1Limits
Spc Temp Stpt 1
Limits
tempSP2Limits
Spc Temp Stpt 2
Limits
tempSP3Limits
Spc Temp Stpt 3
Limits
maxTemp 77.0°F
(25.0°C)
The maximum value that is accepted from
the space temperature setpoint slide*.
50.0 to 95.0°F
(10.0 to 35.0°C)
Type: SNVT_temp_p
Applies a setpoint offset to the setpoint slider
reading, in order to create a deadband
between the heating and cooling temperature
setpoints.
-18.0°F to 18.0°F
(-10.°C to +10.0°C)
Type: SNVT_temp_diff_p
tempOffsetOcc 0°F (0°C) Temperature offset during occupied mode.
tempSP1Offset
Spc Temp Stpt 1
Offset
tempSP2Offset
Spc Temp Stpt 2
Offset
tempSP3Offset
Spc Temp Stpt 3
Offset
tempOffsetUnoc 0°F (0°C) Temperature offset during unoccupied mode.
*Available on some models of the Predator Room Temperature Sensor.
** A value of [0 (STATTEMP),0] indicates unused.