Data Sheet for Product
Document No. 588-154 Page 26 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Selects the source and properties for the PID
setpoint. Must be the same units as
PIDPVSource within each PID.
sourceType spaceSetpt Selects the input variable type.
Enumeration: srcSelSPb
sourceNum
Default values
differ by CP:
pid3SPSource: 3
pid4SPSource: 0
Selects the input variable number.
0 to 6 (0 indicates unused)
nciTemp 32°F (0°C) The temperature network configuration input
(nci) for setpoint. Set the temperature field if
the source of PIDXSPSrc is NCITEMP.
nciPct 0.00%
T
he percent network configuration input (nci)
for setpoint. Set the percent field if the
source of PIDXSPSrc is NCIPCT.
tempOffset 0°F (0°C) The temperature setpoint offset for the PID
selected by PIDXUnits.
pid3SPSource
PID 3 Setpoint
Source
pid4SPSource
PID 4 Setpoint
Source
pctOffset 0.00% The percentage setpoint offset for the PID
selected by PIDXUnits.
Calculates the minimum, maximum or
average of two or more of the measured
space temperatures.
functionType 0 Defines the type of function that you want to
apply.
Minimum, Maximum or Average.
spcTempFncCfg
Spc Temp
Function
Configuration
numInputs 3 Defines the number of space temperatures
that you want to use.
2 or 3 (If you select "2", the controller will
use RTS 1 and RTS 2 for the calculation. If
you select "3", the controller will use all three
temperature sensors for the calculation.
If you select 1, the controller will return
spctemp1.