Data Sheet for Product

Document No. 588-154 Page 24 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines the PID controller gain for PID 3 and
PID 4.
pbTemp Default values
differ by CP:
pid3CtrB: 10°C
pid4CtrB: 0°C
Proportional band if configured for temp in
degrees C.
50.00 to 95.00°F
(10.00 to 35.00°C)
Units: SNVT_temp_diff
pbMult 0 Proportional bad if configured for percent in
multiples of 100%. For example if
proportional band desired is 250%, enter
2.5.
range 0 to 16.3835
Units: SNVT_multiplier
ti Default values
differ by CP:
pid3CtrB: 800 sec
pid4CtrB: 0 sec
Time, in seconds, for integral action. Zero
seconds means no integral action.
0.0 to 6553.4 seconds
pid3CtrB
PID 3 Temp/Pct
Controller
pid4CtrB
PID 4 Temp/Pct
Controller
td
0 seconds Time, in seconds, for derivative action. Zero
seconds means no derivative action.
0.0 to 6553.4 seconds
Selects the source of the disable function. If
the value of the disable source equals the
disable value, then the PID acts as if
overriden to outMinPct in PID1Cfg-PID4Cfg.
type None Selects the disable source type.
Enumeration: disSelA
pid1DisSource
PID 1 Disable
Source
pid2DisSource
PID 2 Disable
Source
pid3DisSource
PID 3 Disable
Source
pid4DisSource
PID 4 Disable
Source
value
0 Selects the disable value.
0=FALSE
1=TRUE