Data Sheet for Product

Document No. 588-154 Page 23 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Configures PID 3 and 4.
reverse Default values
differ by CP:
pid3Cfg: True
pid4Cfg: False
Establishes the reverse direction for the PID.
false for direct acing loop
true for reverse acting loop
unit Temperature Selects the units for the PID proportional
gain setpoint offset and deadband, if used.
Temperature or Percent
outMinPct 0.00% Minimum PID output percent
-163.84% to 163.83%
Unit: SNVT_lev_percent
outMaxPct 100.00% Maximum PID output percent
-163.84% to 163.83%
Unit: SNVT_lev_percent
tempDBand Default values
differ by CP:
pid3Cfg: 0.25°C
pid4Cfg: 0°C
Temperature deadband for the PID.
pctDBand 0.00% Percent deadband for the PID.
pid3Cfg
PID3
Configuration
pid4Cfg
PID4
Configuration
bias 0.00% Bias signal, which is the value in engineering
units of the controller output value (y), when
the process variable (pv) is equal to the
setpoint (sp). NOTE: This input is used for a
Proportional only controller. In this case, Ti
and Td must be set to 0.
Defines the PID controller gain for PID 1 and
PID 2, the dedicated temperature loops.
Pb 10°C Proportional band in degrees C.
50.00 to 95.00°F
(10.00 to 35.00°C)
Units: SNVT_temp_diff
ti 800 seconds Time, in seconds, for integral action. Zero
seconds means no integral action.
0.0 to 6553.4 seconds
pid1CtrB
PID 1 Temp/Pct
Controller
pid2CtrB
PID 2 Temp/Pct
Controller
td 0 seconds Time, in seconds, for derivative action. Zero
seconds means no derivative action.
0.0 to 6553.4 seconds