Data Sheet for Product
Document No. 588-154 Page 20 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines the source of the input for Map 1.
sourceType
spaceTemp Defines the source of the input variable.
Enumeration: srcSelMap
map1Source
Map 1 Source
Select
sourceNum 0 Defines the input variable number.
0 to 6 (0 indicates unused)
Configures the 3-position floating motor
output
travelTime 125 seconds Establishes the end-to-end travel time of the
motor.
30-600 seconds
Unit: SNVT_time_sec
mtr1
Motor 1
mtr2
Motor 2
mtr3
Motor 3
mtr4
Motor 4
reverse FALSE Determines whether or not the motor
outputs should be reversed.
0=False
1=True
Sets the disable function for the digital
output. If the value from the disable source
is equal to the disable value, the motor
operates as if overriden to 0%.
type None Selects the disable input source.
Enumeration: disSelA
mtr1DisSource
Motor 1 Disable
Source
mtr2DisSource
Motor 2 Disable
Source
mtr3DisSource
Motor 3 Disable
Source
mtr4DisSource
Motor 4 Disable
Source
value False Selects the disable value.
0=False
1=True
255=NUL
Defines the values that the input source must
cover to drive the output from its minimum
to its maximum position.
Unit: SNVT_lev_percent
minPercent 0.00% Minimum input range
-163.84% to 163.83%
mtr1Lim
Motor 1 Limits
mtr2Lim
Motor 2 Limits
mtr3Lim
Motor 3 Limits
mtr4Lim
Motor 4 Limits
maxPercent
100.00% Maximum input range
-163.84% to 163.83%