Data Sheet for Product

Document No. 588-154 Page 17 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Selects the function to be performed and
defines the number of inputs to that
component.
functionType Minimum Type of function the component performs.
Minimum, Maximum, or Average
fnc1Cfg
Function 1
Configuration
numInputs 2 The number of inputs to the Function
component.
Range: 2 to 4
Configures the temperature or percent
constant value for use in the Function
component calculation. This value is SourceA
in the calculation.
temperature 32°F (0°C) The temperature constant value for use in
the Function component calculation.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Type: SNVT_temp_p
fnc1ConstA
Function1 Input A
Constant
percent 0.00% The percent constant value for use in the
Function component calculation.
-163.84% to 163.83%
Unit: SNVT_lev_percent
Defines the source of the input for the
Function component.
sourceTypeA spaceTemp Selects the input variable type.**
Enumeration: srcSel4A
sourceNumA 0 Selects the input variable number.
0 to 6 (0 indicates unused)
sourceTypeB spaceTemp Selects the input variable type.**
Enumeration: srcSel4A
sourceNumB 0 Selects the input variable number.
0 to 6 (0 indicates unused)
sourceTypeC spaceTemp Selects the input variable type.**
Enumeration: srcSel4A
sourceNumC 0 Selects the input variable number.
0 to 6 (0 indicates unused)
sourceTypeD spaceTemp Selects the input variable type.**
Enumeration: srcSel4A
fnc1Source
Function 1 Input
Sources
sourceNumD 0 Selects the input variable number.
0 to 6 (0 indicates unused)
Defines the filter time constant for the
physical temperature or percent input.
0 to 6553.4 seconds
tFilter5 0 Defines the filter constant for IN5.
inFilTime2
Input Filter Time
2
tFilter6 0 Defines the filter constant for IN6.