Data Sheet for Product

Document No. 588-154 Page 14 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines the source of the input for the analog
output.
sourceType PID Selects the source of the input signal for the
analog output.
Enumeration: srcCstA
sourceNum Default values
differ by CP:
ao1Source=1
ao2Source=2
ao3Source=3
Selects the input variable number.
NOTE: if nciPct is used as the sourceType,
sourceNum must be set to "1".
0 to 6 (0 indicates unused)
ao1Source
Analog Output 1
Source
ao2Source
Analog Output 2
Source
ao3Source
Analog Output 3
Source
nciPct 0.00% Selects a percentage value to be used as an
input variable constant if nciPct is selected as
source.
-163.84% to 163.83%
Unit: SNVT_lev_percent
bypass1Time
Spc Occ Bypass
Time 1
bypass2Time
Spc Occ Bypass
Time 2
bypass3Time
Spc Occ Bypass
Time 3
60 minutes The amount of time the Predator controller
will remain in bypass mode once an occupant
presses the bypass button* on the Predator
Room Temperature Sensor.
The bypass button in the Three Zone
application is used to disable PID, analog
output, digital output, or motor. It is also
used in combination with the network input
to determine current occupancy state.
0 to 540 minutes
Unit: SNVT_time_min
bypassFncCfg
Bypass Function
Config
3 Indicates whether any of the room
temperature sensors is in bypass mode. Used
as a disable source input to the AO, DO,
Motor and PID components.
Valid Range: 0-3
Units: SNVT Count