Data Sheet for Product

Document No. 588-154 Page 13 of 27
Predator Three Zone Loop Configuration Properties
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Sets the disable function for the analog
output. If the value from the disable source
is equal to the disable value, the output
works as if overriden to 0%. When the
disable condition is no longer true, the
disable will release after the time specified.
type None Defines the source of the disable signal
Enumeration: disDlyA
value False Defines the disable value.
If source is bypass 1-3 or bypass
function, then False=none in bypass
and True=bypass
If source is occupancy 1-3, then
False=occupied and
True=unoccupied
If source is DI or DO, then False=off
and True=on
ao1DisSource
Analog Output 1
Disable Source
ao2DisSource
Analog Output 2
Disable Source
ao3DisSource
Analog Output 3
Disable Source
enableDelay 0 seconds Selects the delay time to release the disable.
0 to 6553.4 seconds
Defines the values that the input source must
cover to drive the output from its minimum
to its maximum position.
Unit: SNVT_lev_percent
minPercent 0.00% Minimum percent input
-163.84% to 163.83%
ao1InRange
Analog Output 1
Input Range
ao2InRange
Analog Output 2
Input Range
ao3InRange
Analog Output 3
Input Range
maxPercent 100.00% Maximum percent input
-163.84% to 163.83%
Defines the values that the output source
must cover to drive the input from its
minimum to its maximum position.
Unit: SNVT_lev_percent
minPercent 0.00% Minimum percent output
0.00 to 100.00%
ao1OutRange
Analog Output 1
Out Range
ao2OutRange
Analog Output 2
Out Range
ao3OutRange
Analog Output 3
Out Range
maxPercent 100.00% Maximum percent output
0.00 to 100.00%