Data Sheet for Product

Wiring Diagram
Optional dmp mtr2
Optional dmp mtr
Siemens GDE131.1P
3-pt floating actuator
violet
red
orange
Y1 (CW)
G (SP)
Y2 (CCW)
Y1 (CW)
G (SP)
Y2 (CCW)
Optional Lighting ctl
Optional Source Temp
Optional Wall Switch
Optional Occ Sensor
QVM Sensor
QVM Sensor
4.7k ohm resistor
4.7k ohm resistor
Y1 (CW)
G (SP)
Y2 (CCW)
Optional Perimeter
heat
Not available
Siemens GDE131.1P
3-pt floating actuator 2
Unused
SSEN0351R1
NOTE: Route wiring from either the bottom opening when using a J-box or from the
base sides as shown in the picture when flat or din rail mounting.
Wiring Recommendations:
IN and AO: 20 to 22 AWG
Page 8 of 13 Document No. 588-023
DO: 18 to 22 AWG
Power: 16 to 18 AWG
LON Network: 22 AWG Level 4
Transformer Requirements:
Type: Class 2, 24 Vac, 50/60Hz
Figure 10. Predator Wiring Diagrams.