Data Sheet for Product
Table Of Contents
- Figure 1. Dual Duct VAV Box with Two Inlet Flow Sensors.
- Figure 2. Dual Duct VAV Box with One Inlet and One Discharge Flow Sensor.
- Features
- Sequence of Operation
- Dual Cold
- Dual Hot
- Morning Warm-up/ Pre-Cool
- Off
- Test/Calibrate
- Occupancy Control
- Special Features
- Hardware Map – Dual Duct VAV/CV
- Wiring Diagram
- Bill of Materials
- Configuration Tables
- Control Mode Interaction Table –Dual Duct VAV with QVM
- Control Mode Interaction Table –Dual Duct CV with QVM
Table 4. QVM Dual Duct Box - Tuning Parameters
Configuration
Parameter
Element Factory Setting Desired Setting
clgDmdCtrB
Pb (5.00°F) 2.78°C
Job Specific
Ti 2000 sec
Job Specific
Td 0 sec
Job Specific
htgDmdCtrB
Pb (10.0°F) 5.56°C
Job Specific
Ti 1000 sec
Job Specific
Td 0 sec
Job Specific
trmFlowCtrB
Pb 4
Job Specific
Ti 12 sec
Job Specific
Td 0 sec
Job Specific
trmFlowHtCtrB
Pb 4
Job Specific
Ti 12 sec
Job Specific
Td 0 sec
Job Specific
Control Mode Interaction Table –Dual Duct VAV with QVM
Control Mode Interaction Table –Dual Duct CV with QVM
Page 12 of 13 Document No. 588-023