Data Sheet for Product

Page 12 of 13 Document No. 588-209
Configuration Property
Language-dependent Name
Element
Programmatic Name
Factory Value
TravelTime 125.0 seconds
Reverse False
trmHtgMotr
Terminal Heating Coil Motor
SyncDirection Close
Pb 0.00
Ti 0 seconds
ventDmdCtrB
Ventilation Demand Cntr Band
Td 0 seconds
ventTempDB
Ventilation Disable Temp DBand
1.11°C
* Available on some models of the Predator Room Temperature Sensor.
Network Configuration Inputs (nci)
NV Name
Language-dependent Name
Element
Programmatic Name
Factory Value
nciPrOffset
Pressure Offset
0.00%
Occupied Cooling Setpoint
(occupied_cool)
73.4°F (23.0°C)
Standby Cooling Setpoint
(standby_cool)
77.0°F (25.0°C)
Unoccupied Cooling
Setpoint
(unoccupied_cool)
82.4°F (28.0°C)
Occupied Heating Setpoint
(occupied_heat)
69.8°F (21.0°C)
Standby Heating Setpoint
(standby_heat)
66.2°F (19.0°C)
nciSetPnts
Occupancy Temperature Setpoints
Unoccupied Heating
Setpoint
(unoccupied_heat)
60.8°F (16.0°C)