Data Sheet for Product

Hardware Map – Heat Pump
Termination Set Parameter Set Element Name I/O Type Factory I/O Setting
StatTemp Inputs statTemp TEMP spaceTemp
StatSetpt Inputs statSetpt TEMP spaceSetptTemp
StatOvrd Inputs statOvrd DI statSwitchDi
In1 Inputs in1 DI, TEMP dischTemp
In2 Inputs in2 DI, TEMP leavingSrcTemp
In3 Inputs in3 DI, PCT, TEMP fanStatusDi
In4 Inputs in4 DI, PCT, TEMP refrigAlarmDi
In5 Inputs in5 DI, PCT, TEMP occSensorDi
In6 Inputs in6 DI, PCT, TEMP condensateOvflwDi
OutA1 Outputs outA1 AO oADmprAo
OutA2 Outputs outA2 AO auxHCoilAo
OutA3 Outputs outA3 AO perimHCoilAo
OutD1 Outputs outD1 DO, FLT_MTR trmFamDo
OutD2 Outputs outD2 DO, FLT_MTR revRelayDo
OutD3 Outputs outD3 DO, FLT_MTR dxStage1Do
OutD4 Outputs outD4 DO, FLT_MTR dxStage2Do
OutD5 Outputs outD5 DO, FLT_MTR auxHCoilFltMtr
OutD6 Outputs outD6 DO, FLT_MTR auxHCoilFltMtr
OutD7 Outputs outD7 DO, FLT_MTR perimHCoilFltMtr
OutD8 Outputs outD8 DO, FLT_MTR perimHCoilFltMtr
In1 through In6 can be used for digital or analog inputs, as follows:
In1 through In6 are dry contact inputs (with resistors)
In1 and In2 also accept 100K ohm inputs
In3, In4, In5, In6 also accept current (4-20 mA) and voltage (0-10 volt) inputs
OutA1, OutA2, and OutA3 are 0-10 volt outputs only
Table 1. Heat Pump Hardware Map
Page 6 of 11
Document No. 588-136