Installation Instructions

Document No. 546-14400
Installation Instructions
February, 2004
CAUTION:
The LRC DOs control 24 Vac loads only. The maximum rating is 12 VA for each DO. Use an interposing
220V 4-relay module (
550-054) for any of the following: VA requirements higher than the maximum;
110 or 220 Vac requirements; DC power requirements; separate transformers used to power the load.
NOTE: Consult with the local representative if terminations are missing or are different.
OUTPUT
SIGNAL
-
NOT USED
NOT USED
FUME HOOD 4
FUME HOOD 3
FUME HOOD 2
FUME HOOD 1
(SHIELD
TAPED BACK)
(SHIELD
TAPED BACK)
FUME HOOD
CONTROLLER
1 FUME HOOD
EXTERNAL FIELD CONNECTIONS
OR
2 TO 4
FUME HOODS
FUME HOOD FLOW MODULE
546-00351
+
-
AO2 FLOW
OUTPUT
SIGNAL
TO
24 VAC
CLASS 2
OUTPUT
SIGNAL
+
FUME HOOD 4
FUME HOOD 3
FUME HOOD 2
FUME HOOD 1
Y8
Y7
Y6
Y5
G
G0
+
-
X2X4
Y4
Y3
Y2
Y1
Y90
Y91
Y92
X1X3
EARTH GROUND NUT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
24 V-AC
RX
TX
FLN TRUNK
+
-
S
BST
RTS
DO1
NO C
DO2
NO C
DO3
NO C
DO4
NO C
DO5
NO C
DO6
NO C
AI5
+
-
DI2
DI6
AO1
+
-
AO2
+
-
AO3
+
-
AI3
+
-
AI4
+
-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
C H EGND
REHEAT VALVE
SPARE DOS
0 - 10 Vdc
CURRENT
POSITION
VO LTAG E
POSITION
VOLTAGE/CURRENT
SWITCH
TO
ACTUATOR
TO
ACTUATOR
J5 J3
AO-E
J2 J1
24 VAC
AO-E MODULE WITH 0-10V
SUPPLY AIR VALVE
J5 J3
AO-E
J2 J1
24 VAC
AO-E MODULE WITH 0-10V
GENERAL EXHAUST AIR VALVE
SPARE (0-10V OR 4-20mA)
SPARE
(100K THERMISTOR ONLY)
N.O. ALARM SWITCH
(OPTIONAL)
N.O. OCCUPANCY SWITCH
(OPTIONAL)
*
*
APPLICATION
2410
ROOM TEMPERATURE
SENSOR
ALARM HORN (OPTIONAL)
AVS 1
SUPPLY
EARTH
GROUND
NUTS
POWER
SUPPLY
TERMINAL
BLOCK
EGND
+
-
TO 24 VAC
CERTIFIED CLASS II
TRANSFORMER
SHIELD
-
+
FLN
TRUNK
EARTH
HOT
NEUTRAL
EARTH
HOT
NEUTRAL
AVS 2
EXHAUST
AUTOZERO
MODULE 1
AUTOZERO
MODULE 2
LEGEND
FACTORY
WIRED
FIELD
WIRED
TEC2410WDR4
24 V
COMMON
24 V HOT
EARTH
GROUND
(GREEN OR
GREEN/YELLOW)
(4-20mA SENSORS REQUIRE SEPARATE
POWER SUPPLY AND ENTIRE CIRCUIT
MUST BE UNGROUNDED)
CONFIRM AI3 AND AI4 DIP-SWITCH
SETTINGS ON CIRCUIT BOARD
UNDER CONTROLLER COVER
See Figure 10 for how to wire a 4-20mA sensor at AI 4 (optional).
Figure 9. Application 2410 Wiring Diagram for LRC (546-14323A) with Onboard AVS.
CAUTION:
If the LRC is not connected as shown, it is not resistant to electrical surges. It is also
susceptible to interference from other equipment.
Page 6 of 7 Siemens Building Technologies, Inc.