Installation Instructions

Document No. 546-14400
Installation Instructions
February, 2004
Wiring Diagrams
CAUTION:
The LRC DOs control 24 Vac loads only. The maximum rating is 12 VA for each DO. Use an interposing
220V 4-relay module (540-147) for any of the following: VA requirements higher than the maximum; 110
or 220 Vac requirements; DC power requirements; separate transformers used to power the load.
NOTE: Consult with the local representative if terminations are missing or are different.
LEGEND
FACTORY
WIRED
FIELD
WIRED
ALARM SWITCH
(OPTIONAL)
0-10V REHEAT
VALVE
(100K THERMISTOR ONLY)
SPARE AI
(0-10V or 4-20mA)
OUTPUT
SIGNAL
-
NOT USED
NOT USED
FUME HOOD 4
FUME HOOD 3
FUME HOOD 2
FUME HOOD 1
(SHIELD
TAPED BACK)
(SHIELD
TAPED BACK)
FUME HOOD
CONTROLLER
1 FUME HOOD
EXTERNAL FIELD CONNECTIONS
OR
2 TO 4
FUME HOODS
FUME HOOD FLOW MODULE
546-00351
TO
24 VAC
CLASS 2
OUTPUT
SIGNAL +
FUME HOOD 4
FUME HOOD 3
FUME HOOD 2
FUME HOOD 1
Y8
Y7
Y6
Y5
G
G0
+
-
X2X4
Y4
Y3
Y2
Y1
Y90
Y91
Y92
X1X3
+
-
AO2 FLOW
OUTPUT
SIGNAL
SPARE
OCCUPANCY SWITCH
(OPTIONAL)
TO
ACTUATOR
TO
ACTUATOR
J5 J3
AO-E
J2 J1
24 VAC
AO-E MODULE WITH 0-10V
GENERAL EXHAUST AIR VALVE
EARTH
HOT
NEUTRAL
J5 J3
AO-E
J2 J1
24 VAC
AO-E MODULE WITH 0-10V
SUPPLY AIR VALVE
EARTH
HOT
NEUTRAL
APPLICATION
2410
14 15 16 14 15 166 7 8 9 10 11 12 136 7 8 9 10 11 12 13 1 2 3 4 51 2 3 4 5
24 V-AC
BSTTXRX
+
-
DO1
NO C
DO2
NO C
DO3
NO C
DO4
NO C
DO5
NO C
DO8
NO C
DO7
NO C
DO6
NO C
AI5
+
-
DI2
DI6
RTS
AVS 1AVS 2AO3
+
-
AO2
+
-
AO1
+
-
AI3
+
-
AI4
+
-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 161 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
EGND+
-
CUR -
RENT
CUR -
RENT
ALARM HORN
(OPTIONAL)
SPARE DOsSPARE DOs
AUTOZERO
MODULE 1
AUTOZERO
MODULE 2
PWR
(4-20mA SENSORS REQUIRE SEPARATE POWER SUPPLY AND ENTIRE CIRCUIT MUST BE UNGROUNDED)
*CONFIRM AI3 AND AI4 DIP-SWITCH SETTINGS ON CIRCUIT BOARD UNDER CONTROLLER COVER
E
H
C
SIGNAL
SIGNAL
GND
GND
PWR
AI4 ("SW1")
AI3 ("S1")
BOTH SWITCHES SHOWN
VOLTAGE POSITION
VOLT-
AGE
VOLT-
AGE
*
S1
SW1
ROOM TEMP
SENSOR
24 V COMMON
24 V HOT
EARTH GROUND
(GREEN OR
GREEN/YELLOW)
EARTH
GROUND
NUT
POWER SUPPLY
TERMINAL BLOCK
TO 24 VAC
CERTIFIED CLASS II
TRANSFORMER
SHIELD
FLN
TRUNK
FLN TRUNK
+
-
+
-
S
+
-
S
+
-
S
+
-
SS
C
H
GND
REMOTE AIR
MODULE
(EXHAUST)
REMOTE AIR
MODULE
(SUPPLY)
2
1
EARTH
GROUND
NUT
TEC-RAM2410WDR1
SUPPLYEXHAUST
See Figure 10 for how to wire a 4-20mA sensor at AI 4 (optional).
Figure 8. Application 2410 Wiring Diagram for LRC (550-767B) requiring Remote Air Modules.
CAUTION:
If the LRC is not connected as shown, it is not resistant to electrical surges. It is also
susceptible to interference from other equipment.
Siemens Building Technologies Page 5 of 7