Data Sheet for Product

Document No. 588-154 Page 25 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Selects the source of the PID process
variable. Must be the same units as
PIDSPSource within each PID.
sourceType spaceTemp Selects the input variable type.
Enumeration: srcSelPVA
pid1PVSource
PID 1 Process
Variable Source
pid2PVSource
PID 2 Process
Variable Source
sourceNum Default values
differ by CP:
pid1PVSource: 1
pid2PVSource: 2
Selects the input variable number.
0 to 6 (0 indicates unused)
Selects the source of the PID process
variable. Must be the same units as PIDXSP
within each PID.
sourceType spaceTemp Selects the input variable type.
Enumeration: srcSelPVb
pid3PVSource
PID 3 Process
Variable Source
pid4PVSource
PID 4 Process
Variable Source
sourceNum Default values
differ by CP:
pid3PVSource: 3
pid4PVSource: 0
Selects the input variable number.
0 to 6 (0 indicates unused)
Selects the source and properties for the PID
setpoint. Must be the same units as
PIDXPVSource within each PID (X=1-4).
sourceType spaceSetpt Selects the input variable type.
Enumeration: srcSelSPa
sourceNum Default values
differ by CP:
pid1SPSource: 1
pid2SPSource: 2
Selects the input variable number.
0 to 6 (0 indicates unused)
nciTemp 32°F (0°C) The temperature network configuration input
(nci) for setpoint. Set the temperature field if
the source of PIDXSPSrc is NCITEMP (x=1-
4).
pid1SPSource
PID 1 Setpoint
Source
pid2SPSource
PID 2 Setpoint
Source
tempOffset 0°F (0°C) The temperature setpoint offset for the PID.