Data Sheet for Product
Document No. 588-154 Page 22 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
occ1Default
Spc Occ 1 Default
occ2Default
Spc Occ 2 Default
occ3Default
Spc Occ 3 Default
unoccupied If the network occupancy input is NUL, this
value is used in its place. Used in
conjunction with byass to determine the
occupancy state.
Valid selections: Occupied or Unoccupied
(occupT )
Unit: SNVT_occupancy
Configures PID 1 and 2.
reverse True Establishes the reverse direction for the PID.
false for direct acing loop
true for reverse acting loop
outMinPct 0.00% Minimum PID output percent
-163.84% to 163.83%
Unit: SNVT_lev_percent
outMaxPct 100.00% Maximum PID output percent
-163.84% to 163.83%
Unit: SNVT_lev_percent
tempDBand 0.25°C Temperature deadband for the PID.
pid1Cfg
PID1
Configuration
pid2Cfg
PID2
Configuration
bias 0.00% Bias signal, which is the value in engineering
units of the controller output value (y), when
the process variable (pv) is equal to the
setpoint (sp).
NOTE: This input is used for a Proportional
only controller. In this case, Ti and Td must
be set to 0.