Data Sheet for Product
Document No. 588-154 Page 21 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Selects the input source for the 3-position
floating motor
sourceType Default values
differ by CP:
mtr1Source-
mtr3Source:PID
mtr4Source:
nciPercent
Selects the input variable type.
Enumeration: srcCstA
sourceNum Default values
differ by CP:
mtr1Source and
mtr4Source:1
mtr2Source:2
mtr3Source:3
Selects the input variable number.
0 to 6 (0 indicates unused)
mtr1Source
Motor 1 Source
mtr2Source
Motor 2 Source
mtr3Source
Motor 3 Source
mtr4Source
Motor 4 Source
nciPct 0.00% Selects a percentage value to be used as an
input variable constant if NCI_PCT is selected
as source.
-163.84% to 163.83%
Unit: SNVT_lev_percent
The value used by the controller if a network
input is NUL.
temp1 32°F
(0°C)
Fail value for nviTemp1.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
temp2 32°F
(0°C)
Fail value for nviTemp2.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
temp3 32°F
(0°C)
Fail value for nviTemp3.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
temp4 32°F
(0°C)
Fail value for nviTemp4.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
pct1 0.00% Fail value for nviPct1.
-163.84% to 163.83%
Unit: SNVT_lev_pct
nvFailValue
Network Input
Fail Values
pct2 0.00% Fail value for nviPct2.
-163.84% to 163.83%
Unit: SNVT_lev_pct