Data Sheet for Product

Document No. 588-154 Page 19 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines the output percent or temperature
breakpoints for the Map component.
Breakpoints must be used in consecutive
order. For example, if you are using 2
breakpoints, you must use A and B. If you
are using 3 breakpoints, you must use A, B
and C.
tempA 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempB 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempC 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempD 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
pctA 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
pctB 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
pctC 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
map1BrkOut
Map 1 Output
Breakpoint
pctD 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
Defines the number of breakpoints and input
and output type for Map 1.
numBrkpts 2 Number of breakpoints for the input range.
2-4
Unit: SNVT_count
inType Temperature Unit type of the input.
Temperature=0
Percent=1
map1Cfg
Map 1
Configuration
outType Temperature Unit type of the output.
Temperature=0
Percent=1