Data Sheet for Product

Document No. 588-154 Page 18 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines the input temperature pr percent
breakpoints for the Map component.
Breakpoints must be used in consecutive
order. For example, if you are using 2
breakpoints, you must use A and B. If you
are using 3 breakpoints, you must use A, B
and C, etc.
tempA 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempB 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempC 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
tempD 32°F
(0°C)
Temperature breakpoint.
-459.706°F to 621.788°F
(-273.17°C to 327.66°C)
Unit: SNVT_temp_p
pctA 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
pctB 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
pctC 0.00% Percent breakpoint.
-163.84% to 163.83%
Unit: SNVT_lev_percent
map1BrkIn
Map 1 Input
Breakpoint
pctD 0.00% Percent breakpoint.
-163.84 to 163.83%
Unit: SNVT_lev_percent