Data Sheet for Product
Document No. 588-154 Page 16 of 27
Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
type None Selects the disable input source.
Enumeration: disDlyA
value False Selects the disable value.
If source is bypass 1-3 or bypass
function, then False=none in bypass
and True=bypass
If source is occupancy 1-3, then
False=occupied and
True=unoccupied
If source is DI or DO, then False=off
and True=on
Disable Source
do4DisSource
Digital Output 4
Disable Source
do5DisSource
Digital Output 5
Disable Source
do6DisSource
Digital Output 6
Disable Source
do7DisSource
Digital Output 7
Disable Source
do8DisSource
Digital Output 8
Disable Source
enableDelay 0 seconds Selects the delay time to release the disable
function.
0 to 6553.4 seconds
Defines the source of the input for the digital
output.
sourceType nciPercent Selects the source of the input signal for the
digital output.
Enumeration: srcCstA
sourceNum 1 Selects the input variable number.
NOTE: If nciPct is used as the sourceType,
then sourceNum must be set to "1".
0 to 6 (0 indicates unused)
do1Source
Digital Output 1
Source
do2Source
Digital Output 2
Source
do3Source
Digital Output 3
Source
do4Source
Digital Output 4
Source
do5Source
Digital Output 5
Source
do6Source
Digital Output 6
Source
do7Source
Digital Output 7
Source
do8Source
Digital Output 8
Source
nciPct
0.00% Selects a percentage value to be used as an
input variable constant if NCI_PCT is selected
as source.
-163.84% to 163.83%
Unit: SNVT_lev_percent