Configuration
Property
Language-
dependent Name
Element
Programmatic
Name
Factory Value Description
Defines how the digital output responds to its
input signal.
type Deadband Selects the manner in which the digital
output (DO) uses the input.
Deadband or PWM
pWMMinPct 0.00% Defines the input for 0% duty cycle. When
the input source is below this level, the DO
will operate with 0% duty cycle if configured
for PWM.
-163.84% to 163.83%
Unit: SNVT_lev_percent
pWMMaxPct 100.00% Defines the input for 100% duty cycle. When
the input source is above this level, the DO
will operate with 100% duty cycle if DO is
configured for PWM.
-163.84% to 163.83%
Unit: SNVT_lev_percent
dBandPctOn 67.00% Defines the ON values for the deadband
outputs. When the input source goes above
this level, the DO will stay ON until the input
source goes below dBandPctOff, if DO is
configured for deadband.
-163.84% to 163.83%
Unit: SNVT_lev_percent
dBandPCtOff 33.00% Defines the OFF values for the deadband
outputs. When the input source goes below
this level, the DO will stay OFF until the input
source goes above dBandPctOn, if DO is
configured for deadband.
0.00 to -163.84% to 163.83%
Unit: SNVT_lev_percent
do1Cfg
Digital Output 1
Configuration
do2Cfg
Digital Output 2
Configuration
do3Cfg
Digital Output 3
Configuration
do4Cfg
Digital Output 4
Configuration
do5Cfg
Digital Output 5
Configuration
do6Cfg
Digital Output 6
Configuration
do7Cfg
Digital Output 7
Configuration
do8Cfg
Digital Output 8
Configuration
pWMCycleTime 600 seconds Defines the cycle time for a digital output
during a PWM cycle. The cycle time is the
total ON and OFF time for a single cycle of
the digital output.
0.0 to 6553.4 seconds
Unit: SNVT_time_sec
do1DisSource
Digital Output
Disable Source
do2DisSource
Digital Output 2
Disable Source
do3DisSource
Digital Output 3
Determines if and how the disable function
will operate. If the value from the disable
source is equal to the disable value, the
output works as if overriden to OFF. When
the disable condition is no longer true, the
disable will release after the time specified.