Data Sheet for Product
Document No. 588-154 Page 10 of 27
Hardware Map Factory Settings
The Predator Three Zone Loop controller is only available on the full-point
platform. For more information concerning the various Predator hardware
platforms, see the Predator Owners Manual.
Configuration
Property
Element Input/Output Factory Hardware Setting
StatTemp1 TEMP spaceTemp1
StatSetpt1 TEMP spaceSetpt1
StatOvrd1 DI statSwitchDI1
StatTemp2 TEMP spaceTemp2
StatSetpt2 TEMP spaceSetpt2
StatOvrd2 DI statSwitchDI2
StatTemp3 TEMP spaceTemp3
StatSetpt3 TEMP spaceSetpt3
StatOvrd3 DI statSwitchDI3
IN5 DI, PCT, TEMP in5Temp
inputs
IN6 DI, PCT, TEMP in6Temp
OUTA1 AO ao1
OUTA2 AO ao2
OUTA3 AO ao3
OUTD1 DO, FLT_MTR motor1
OUTD2 DO, FLT_MTR motor2
OUTD3 DO, FLT_MTR motor3
OUTD4 DO, FLT_MTR motor4
OUTD5 DO, FLT_MTR motor5
OUTD6 DO, FLT_MTR motor6
OUTD7 DO, FLT_MTR do7
outputs
OUTD8 DO, FLT_MTR do8