Data Sheet for Product
Document No. 588-154 Page 9 of 27
Wiring Diagram
Three Zone Predator Wiring Base.
Note: Route wiring from either the bottom opening when
using a J-box or from the base sides as shown in the picture
when flat or din rail mounting. The image above is for
illustrative purposes only
Wiring Recommendations
• IN and AO: 20-22 AWG
• DO: 18-22 AWG
• Power: 16-18 AWG
• LON Network: 22 AWG Level 4
Transformer Requirements
• Type: Class 2, 24 VAC, 50/60Hz