Data Sheet for Product

Document No. 588-023 Page 7 of 13
Perimeter Heat
This application also supports the optional control of perimeter heat. The algorithm supports analog,
three-point floating, pulse width modulation, and on/off control of the perimeter heat. Perimeter heat
operates independently of terminal airflow.
Hardware Map – Dual Duct VAV/CV
Table 1. Hardware Map.
Termination
Set
Element Name I/O Type Factory I/O Setting
StatTemp statTemp TEMP SPACE_TEMP
StatSetpt statSetpt TEMP SPACE_STPT_TEMP
StatOvrd statOvrd DI STAT_SWITCH_DI
In1 in1 DI, TEMP SOURCE_TEMP
In2 in2 DI, TEMP SPARE1_TEMP
In3 in3 DI, PCT, TEMP WALL_SWITCH_DI
In4 in4 DI, PCT, TEMP OCC_SENSOR_DI
In5 in5 DI, PCT, TEMP VELOCITY_EXT2_PCT
In6 in6 DI, PCT, TEMP VELOCITY_EXT1_PCT
OutA1 outA1 AO FLOW_DMPR_AO
OutA2 outA2 AO FLOW_DMPR2_AO
OutA3 outA3 AO OUT_UNUSED
OutD1 outD1 DO, FLT_MTR FLOW_DMPR_FLT_MTR
OutD2 outD2 DO, FLT_MTR FLOW_DMPR_FLT_MTR
OutD3 outD3 DO, FLT_MTR FLOW2_DMPR_FLT_MTR
OutD4 outD4 DO, FLT_MTR FLOW2_DMPR_FLT_MTR
OutD5 outD5 DO, FLT_MTR PERIM_H_COIL_FLT_MTR
OutD6 outD6 DO, FLT_MTR PERIM_H_COIL_FLT_MTR
OutD7 outD7 DO, FLT_MTR OUT_UNUSED
OutD8 outD8 DO, FLT_MTR SPC_LIGHTS_DO
In1 through In6 can be used for digital or analog inputs, as follows:
In1 through In6 are dry contact inputs (with resistors)
In1 and In2 also accept 10K ohm inputs
In3, In4, In5, and In6 also accept current (4 to 20 mA) and voltage (0 to 10 volt) inputs
A1, A2, and A3 are 0 to 10 volt outputs only.