Data Sheet for Product

Document No. 588-209 Page 9 of 13
Configuration Table
The following table lists all of the configuration properties (CPs) available with this
application. For more information on how to set these properties, please consult the
Predator VAV with CO2 Application Guide.
Configuration Properties – VAV with CO2
Configuration Property
Language-dependent Name
Element
Programmatic Name
Factory Value
actDisplay
Actuator Display Selection
command
airTermType
Type of Air Terminal
no_Fan
bypassTime
Bypass Time
60 minutes
Pb
2.78°C (5.0°F)
Ti 2000.0 seconds
clgDmdCtrB
PID Controller Gain of the Cooling
Controller
Td 0.0 seconds
cO2SensRng
Space CO2 Sensor Range
0 ppm
ductArea
Trm Duct Area
1.076 ft
2
(0.1 m
2
)
fanUnoccHtg
Unocc Heat Fan Operation
modulate
fanWarmup
Warmup Operation for Fan
on
TravelTime 90.0 sec
Reverse False
flowDmprMotr
Trm Flow Damper Motor
SyncDirection Close
SaturationLoad 110%
PrctDeadband 2%
flowDmprSat
Trm Flow Damper Saturation
TimeDelay 10 min
PercentOn 110.00%
flowFanRq
Flow Setpoint Deadband
PercentOff 100.00%
flowUnoccHtg
Unoccupied Heat Flow Operation
modulate
Enable TRUE
DmdAtMin 0.00%
flowVav
Flow VAV Element
DmdAtMax 100.00%
flowWarmup
Warmup Operation for Flow
Off
hCoilFanRq
Heat Coil Fan Request
PercentOn 3.00%