Data Sheet for Product

Document No. 588-209 Page 7 of 13
Sample Wiring Diagram for VAV with CO2 Application
Configuration
Note: Route wiring from either the bottom opening when using a J-box or from the base sides as shown
in the picture when flat or din rail mounting. The image above is for illustrative purposes only
Wiring Recommendations:
IN and AO: 20 to 22 AWG
DO: 18 to 22 AWG
Power: 16 to 18 AWG
LON Network: 22 AWG
Level 4
Transformer Requirements:
Type: Class 2, 24 VAC, 50/60Hz
Predator Wiring Diagrams (Full Point Board Shown)