Data Sheet for Product
Table Of Contents
Page 6 of 13 Document No. 588-209
Hardware Map – VAV with CO2
Sample Hardware Map for the VAV with CO2 Application Configuration
Configuration
Property
Element Input/Output
Type
Factory Hardware Setting Desired Setting
Settings that need to be
changed from the factory
defaults are shown in BOLD face
type.
statTempOffset - 0°F
0°C
0°F
0°C
inStat
statSetptOffset - 0°F
0°C
0°F
0°C
statTemp TEMP SPACE_TEMP SPACE_TEMP
statSetpt TEMP SPACE_SETPT_OFFSET_TEMP SPACE_SETPT_OFFSET_TEMP
statOvrd DI STAT_SWITCH_DI STAT_SWITCH_DI
IN1 DI, TEMP SPARE2_IN
IN_UNUSED
IN2 DI, TEMP IN_UNUSED IN_UNUSED
IN3 DI, PCT,
TEMP
OCC_SENSOR_DI
IN_UNUSED
IN4 DI, PCT,
TEMP
SPACE1_IN
IN_UNUSED
IN5 DI, PCT,
TEMP
SPACE_CO2_PCT SPACE_CO2_PCT
Inputs
IN6 PCT ONBD_PRESSURE_PCT ONBD_PRESSURE_PCT
OUTA1 AO FLOW_DMPR_AO
OUT_UNUSED
OUTA2 AO TRM_H_COIL_AO
OUT_UNUSED
OUTD1 DO,
FLT_MTR
FLOW_DMPR_FLT_MTR FLOW_DMPR_FLT_MTR
OUTD2 DO,
FLT_MTR
FLOW_DMPR_FLT_MTR FLOW_DMPR_FLT_MTR
OUTD3 DO,
FLT_MTR
TRM_H_COIL_FLT_MTR TRM_H_COIL_FLT_MTR
OUTD4 DO,
FLT_MTR
TRM_H_COIL_FLT_MTR TRM_H_COIL_FLT_MTR
OUTD5 DO,
FLT_MTR
PERIM_H_COIL_FLT_MTR
OUT_UNUSED
OUTD6 DO,
FLT_MTR
PERIM_H_COIL_FLT_MTR
OUT_UNUSED
OUTD7 DO,
FLT_MTR
TRM_FAN_DO
OUT_UNUSED
outputs
OUTD8 DO,
FLT_MTR
SPARE1_OUT
OUT_UNUSED