Data Sheet for Product
Table Of Contents
Document No. 588-209 Page 5 of 13
Optional Functions
Room Temperature Sensor Sharing
The Predator Room Temperature Sensor may share its value with other controllers
on the LonTalk network via a network binding. This is most commonly done when
multiple terminal units serve a room or area.
Occupancy Sensor/Wall Switch
An optional maintained contact wall switch may be used to control the occupancy mode of
a room. Rooms with variable occupancy (conference rooms, etc.) can use this device to
control occupancy and the lights with one switch.
Another useful option is to utilize an occupancy sensor to control the occupancy
mode of the Predator controller. The function of this device would be similar to the
wall switch above, but an occupant entering the room would not perform any manual
action to put the room into occupied mode. If the schedule is in the occupied mode
and the occupancy sensor does not detect people in the room, the room will go into
the standby mode enabling energy savings while maintaining occupant comfort.
Analog Damper Actuator
The standard application is setup to use a Siemens GDE or GLB, or similar 3-point
floating actuator for air volume control. Alternatively, A Siemens Open Air
TM
or similar
damper actuator could be utilized if 0-10 VDC modulating control is desired.
Perimeter Heat
This application also supports the optional control of perimeter heat. The algorithm
supports analog, 3-point floating, pulse width modulation, and on/off control of the
perimeter heat. Perimeter heat operates independently of terminal airflow or the
current state of the terminal fan.