Data Sheet for Product

Document No. 588-209 Page 11 of 13
Configuration Property
Language-dependent Name
Element
Programmatic Name
Factory Value
DmdAtMin 0.00%
DmdAtMax 100.00%
TravelTime 125 seconds
Reverse False
perimHtgMotr
Perimeter Htg Coil Motor
SyncDirection close
sensConstVAV
Trm Flow Gain
1
seriesStDelay
Series Fan Start Delay
0.0 seconds
NeededToCool 18.0°C (64.4°F)
sourceTempLim
Heating Cooling Limits
NeededToHeat 25.0°C (77.0°F)
spaceCO2Stpt
Space CO2 Setpoint
0 ppm
spare1In
spare2In
spare1Out
spare2Out
statSwitchEn
Local Occupancy Switch Enable
False
stptDialEn
Local Temperature Setpoint Dial Enable
False
stptOffstSpan
Spc Temp Stpt Offset Span
2.0°C
MinTemp 19.0°C (66.2°F)
tempStptLim
Space Temperature Setpoint Dial Limits
MaxTemp 25.0°C (77.0°F)
saturationLoad 110%
tempDeadband
10°C (18°F)
trmCoolSat
Terminal Cooling Saturation
timeDelay 10 min
Pb 4
Ti 12.0 seconds
trmFlowCtrB
Trm Flow Cntr Band
Td 0.0 seconds
SaturationLoad 110%
TempDeadband 2°C (3.6°F)
trmHeatSat
Terminal Heat Saturation
TimeDelay 10 min
Enable False
DmdAtMin 0.00%
trmHtgCoil
Terminal Heating Coil Element
DmdAtMax 100.00%
trmHtgEnrgy
Energy Source for Terminal Heating Coil
Hot Water