Data Sheet for Product
Table Of Contents
Configuration Tables
The application configuration tables below are typical for a Heat Pump controller.
App Component Configuration Parameter Element Factory Setting Desired Setting
Heat Pump Core
htgClgSwit
dmdDeadband 1%
tmpDeadband 0.5 °C
timeDelay 6 min
maxStDelay
minutes 10 min
setPnts
Unoccupied cooling
setpoint
82.4°F (28.0°C)
Standby cooling setpoint 77.0°F (25.0°C)
Occupied cooling
setpoint
73.4°F (23.0°C)
Occupied heating
setpoint
69.8°F (21.0°C)
Standby heating setpoint 66.2°F (19.0°C)
Unoccupied heating
setpoint
60.8°F (16.0°C)
Space Temp Sensing statSwitchEn UNVT_boolean TRUE
stptDialEn UNVT_boolean FALSE
tempStptLim minTemp 19.0 °C
maxTemp 25.0 °C
mixedLowLimEn
FALSE
enable
39.20°F (4.00°C)
mixedLLStpt
disable
46.40°F (8.00°C)
Mixed Air
Temperature Sensing
mixedLLDelay
15.0 sec
Safeties loTempLatch FALSE
econDBand 1.0 °C
oACtrlDXOn MODULATE
oACtrlSrc MIXED
minTemp 53.60°F (12.00°C)
oACtrlStptRng
maxTemp 64.40°F (18.00°C)
Outdoor Air Damper
Control
OADFanReq percentOn 3%
percentOff 0%
oADmpr2PosEn FALSE
oaDmpr enable TRUE
dmdAtMin 0%
dmdAtMax 40%
oADmprMtr travelTime 90 sec
reverse FALSE
oADmprNPurg
MODULATE
oADmprPcool
MODULATE
oADmprUnocc
MODULATE
oADmprMin 10%
hPSrcTemp neededToCool
32.0 °C
Source State and
Temp
neededToHeat
4.0 °C
Document No. 588-136 Page 9 of 11