Data Sheet for Product

App Component Configuration Parameter Element Factory Setting Desired Setting
Fan Control
dxFanOffDly
10 sec
fanMinOn
2 min
fanOcc
ON
fanStatusEn
FALSE
fanStby
MODULATE
fanWrmup
ON
hCoilFanRq percentOn 3%
percentOff 0%
htgFanDelay 10 min
enable 50.00°F (10.00°C)
dXClgLockout
disable 46.4°F (8.00°C)
dXFanOffDly 10 sec
Terminal DX Heating
and Cooling with
Reversing Relay
dXMinOffTime
2 min
dXMinOnTime
2 min
dXStageDelay
3 min
numDXStages
1
revRelayEn
TRUE
trmClgCoil
enable TRUE
dmdAtMin 50%
dmdAtMax 100%
trmHtgCoil
enable TRUE
dmdAtMin 0%
dmdAtMax 100%
Auxiliary Heat auxHtgCoil enable FALSE
dmdAtMin 0%
dmdAtMax 100%
auxHtgMtr
travelTime 125 sec
reverse FALSE
auxLockout
enable
20.0 °C
disable
22.0 °C
hStageCyc
10 min
numHStages 0
Lighting Control lightsLag
Perimeter Heating
numPerimStgs 0
perimHUnocc
MODULATE
perimHWrmup
CYCLE
perimHtgCoil
enable FALSE
dmdAtMin 0%
dmdAtMax 100%
perimHtgMtr travelTime 125 sec
reverse FALSE
Occupancy Control bypassTime 60 min
occSensorEn
FALSE
statSwitchEn FALSE
wallSwitchEn
FALSE
Spare Digital Output
Spare Analog Output
Spare Digital Reading
Spare Analog Temp
Page 10 of 11
Document No. 588-136