Data Sheet for Product

Hardware Map – Unit Vent with Dehumidification
Configuration
Property
Element Input/Output
Factory Hardware Setting (Unit
Ventilator CW)
StatTemp TEMP SPACE_TEMP
StatSetpt TEMP SPACE_SETPT_TEMP
StatOvrd DI STAT_SWITCH_DI
IN1 DI, TEMP DISCH_TEMP
IN2 DI, TEMP MIXED_TEMP
IN3 DI, PCT, TEMP CONDENSATE_OVRFLW_DI
IN4 DI, PCT, TEMP SPACE_HUMIDITY_PCT
IN5 DI, PCT, TEMP FAN_STATUS_DI
inputs
IN6 DI, PCT, TEMP SPARE_1_IN
OUTA1 AO OA_DMPR_AO
OUTA2 AO TRM_H_COIL_AO
OUTA3 AO TRM_C_COIL_AO
OUTD1 DO, FLT_MTR TRM_FAN_DO
OUTD2 DO, FLT_MTR HI_SPEED_TRM_FAN_DO
OUTD3 DO, FLT_MTR EXH_FAN_DO
OUTD4 DO, FLT_MTR TRM_H_COIL_FLT_MTR
OUTD5 DO, FLT_MTR TRM_H_COIL_FLT_MTR
OUTD6 DO, FLT_MTR TRM_C_COIL_FLT_MTR
OUTD7 DO, FLT_MTR TRM_C_COIL_FLT_MTR
outputs
OUTD8 DO, FLT_MTR SPARE_OUT1
Table 1. Hardware Map
Page 6 of 12
Document No. 588-153