Data Sheet for Product

Dehumidification Sequence Diagram
100% Open
Damper
Minimum
0%
Heating
Valve
Cooling
Valve
Outdoor Air
Damper
Optional Functions
Room Temperature Sensor Sharing
The Predator Room Temperature Sensor may share its value with other controllers on the
LONTalk
®
network via a network binding. This is most commonly done when multiple terminal
units serve a room or area.
Wall Switch
An optional maintained contact wall switch may be used to control the occupancy mode of a
room. Rooms with variable occupancy (conference rooms, etc.) can use this device to control
occupancy and the lights with one switch.
Occupancy Sensor
Another useful option is to utilize an occupancy sensor to control the occupancy mode of the
Predator controller. The function of this device would be similar to the wall switch above, but
an occupant entering the room would not perform any manual action to put the room into
occupied mode. If the schedule is in the occupied mode and the occupancy sensor does not
detect people in the room, the room will go into the standby mode enabling energy savings
while maintaining occupant comfort.
Analog Damper Actuator
The Predator supports use of a Siemens OpenAir
GMA161.1U (or GMA161.1P – plenum
type) or similar damper actuator when 0-10 VDC position control is desired.
Perimeter Heat
This application also supports the optional control of perimeter heat. The algorithm supports
analog, 3-point floating, pulse width modulation, and on/off control of the perimeter heat.
Perimeter heat operates independently of terminal airflow or the current state of the terminal
Page 4 of 12
Document No. 588-153