Data Sheet for Product

Chart 2: Night Purge, Pre-cool, Off, Fan Only, Condensate Overflow, Fan Proof and Low Temp Modes
Night
Purge
Pre-Cool Off Fan Only
Condensate
Overflow
Fan Proof
Failure
Low Temp
Term Htg
Coil (HW)
Closed Closed Closed Closed Closed Closed Open
Staged
Heat (Elec)
Off Off Off Off Off Off Off
Fan
Demand On
Cycle
Off On Off Off Off
OA Dmpr
Cool Loop
Max
Off
Cool Loop
Max
Closed
Closed Closed Closed Closed Closed
Trm Clg
Coil
Cool Loop
Cycle
Off
Cool Loop
Max
Off
Closed Closed Closed Closed Open
Relief Fan
Demand Demand Off Off Off Off Off
Color Key: Red = OFF (not used); Green = Active (fixed in application); Yellow = Selectable (configurable)