Data Sheet for Product

Control Mode Interaction Table
Due to the large horizontal size of the control mode chart, it is split into the following two parts:
Chart 1: Dehumidification, Heat, Warm-up and Cooling Modes
Chart 2: Night Purge, Pre-cool, Off, Fan Only, Condensate Overflow, Fan Proof
Failure and Low Temp Modes
Control Mode Chart 1 (Dehumidification, Heat, Warm-up and Cool Modes)
Dehumid Heat Cool
Occ Unocc Occ Unocc
Warmup
Occ Unocc
Term Htg
Coil (HW)
Heat Loop Heat Loop
Cycle
Off
Heat Loop Heat Loop
Cycle
Off
Heat Loop
Cycle
Max
Off
Closed Closed
Staged
Heat (Elec)
Heat Loop Heat Loop
Cycle
Off
Heat Loop Heat Loop
Cycle
Off
Heat Loop
Cycle
Max
Off
Off Off
Fan
On
Cycle On
Cycle
Cycle On
Cycle
On
Cycle
Cycle
OA Dmpr
Min Closed Min Closed Closed Cool Loop
Closed
Cool Loop
Closed
Trm Clg
Coil
Open Open Closed Closed Closed Cool Loop
Cool Loop
Cycle
Off
Relief Fan
Demand Off Demand Off Off Demand Demand
Color Key: Red = OFF (not used); Green = Active (fixed in application); Yellow = Selectable (configurable)
Page 10 of 12
Document No. 588-153