Installation Instructions
Table Of Contents
Configuration Tables
The application configuration tables below are typical for a VAV AHU controller.
Application Component Variable Name Element Factory Setting
hVACSeqDelay 5 minutes
startDelay 0 minutes
Small VAV Air Handler
Core
testTime
180 seconds
TravelTime 125 seconds
clgCoilMtr
Reverse False
Pb 50°F (10.0°C)
Ti 300 seconds
coolCoilCtl
Td 0 seconds
coolCoilEn False
coolDeadBand 0.90°F (0.50°C)
Enable 32°F (0°C)
Cooling Coil CW
coolLockout
Disable 14°F (-10°C)
dAClSP 59°F (15°C)
dAHtSP 95°F (35°C)
dAResetSrc 0
maxDAClIn 68°F (20°C)
maxDAClPct 0.0%
maxDAClSP 68°F (20°C)
maxDAHtIn 68°F (20°C)
maxDAHtPct 100.0%
maxDAHtSP 104°F (40°C)
minDAClIn 68°F (20°C)
minDAClPct 100.0%
minDAClSP 59°F (15°C)
minDAHtIn 68°F (20°C)
minDAHtPct 0.0%
Discharge Air Temp
Sensing
minDAHtSP
50°F (10°C)
ductStatSP 250 Pa
ductPresCtl
Pb 500 Pa
Ti 20 seconds
Td 0 seconds
Duct Pressure Sensing
ductPresRange
498 Pa
DX Cooling
coolDeadBand
90°F (50°C)
Enable 32°F (0°C)
coolLockout
Disable 14°F (-10°C)
dXMinOffTime 2 minutes
dXMinOnTime
2 minutes
numDXStages
0
dXStageDelay
3 minutes
Fan Control
fanRampTime
15 seconds
fanStatusEn
False
Document No. 588-150 Page 9 of 11