Installation Instructions

Wiring Diagram
Note: Route wiring from either the bottom opening when using a J-box or
from the base sides as shown in the picture when flat or din rail mounting.
The image above is for illustrative purposes only
Wiring Recommendations:
IN and AO: 20 to 22 AWG
DO: 18 to 22 AWG
Power: 16 to 18 AWG
LON Network: 22 AWG Level 4
Transformer Requirements:
Type: Class 2, 24 VAC, 50/60Hz
Figure 3. Predator Wiring Diagrams
Document No. 588-150 Page 7 of 11