Installation Instructions
Table Of Contents
Document No. 588-150 Page 11 of 11
Control Mode Interaction Table
Device Mode
Occupied Unoccupied Safety
Off Fan
Only
Starting
(Fan Proof)
cool heat cool Idle heat low
temp
other
safety
Fan off mod mod mod mod mod off mod off off
OA damper close close close mod min mod close close close close
DX off off off stage off mod off off off off
Stage heat off off off stage stage stage off stage off off
Heat valve off off select mod mod mod select mod open off
Color Key: Red = OFF (not used); Green = Active (fixed in application); Yellow = Selectable (configurable)
Notice: Information in this document is based on specifications believed correct at the time of publication. The right is reserved
to make changes as design improvements are introduced.
Credits: Staefa Control System, Raptor, Predator, and TALON are trademarks of Siemens Building Technologies, Inc. Niagara
Framework is a registered trademark of Tridium, Inc. Other products and company names herein may be the trademarks of
their respective owners.
Siemens Building Technologies, Inc.
HVAC Products
1000 Deerfield Parkway
Buffalo Grove, Illinois 60089
Phone 847-215-1000
www.staefa.com
Copyright 2001 by Siemens Building Technologies, Inc.