Installation Instructions
Table Of Contents
Application Component Variable Name Element Factory Setting
Modulating Heat
Pb 68°F (20°C)
Ti 300 seconds
heatCoilCtl
Td 0 seconds
heatCoilEn
False
TravelTime 125.0 seconds
htgCoilMtr
Reverse FALSE
heatDeadBand
0.90°F (0.50°C)
Enable 68°F (20°C)
heatLockout
Disable 71.6°F (22°C)
heatUnit Off
econControl Enabled
econDBand 1.8°F (1°C)
Source SRC_RETURN_TEMP
FixedTemp 68°F (20°C)
econRef
Offset 35.6°F (2°C)
Pb 95°F (35°C)
Ti 200 seconds
oADmprCntr
Td 0 seconds
oAMinPos
0%
oAReducedPos
0%
oATempAdaptEn
Enable
vDmdDesign
100%
OA Damper Control with
Mixed Air
vDmdReduced
0.0%
Occupancy Control
bypassTime
60 minutes
statSwitchEn
False
OccupiedClg 73°F (23°C)
StandbyClg 77°F (25°C)
UnoccupiedClg 82°F (28°C)
OccupiedHtg 70°F (21°C)
StandbyHtg 66°F (19°C)
setpoints
UnoccupiedHtg 61°F (16°C)
unocDeadBand
3.6°F (2°C)
Duration 0 minutes
OutTemp 50°F (10°C)
warmupTrig
InTemp 62°F (17°C)
hiPressLatch
Enable
Safeties
loTempLatch
Enable
Staged Heat
heatDeadBand
0.90°F (0.50°C)
Enable 68°F (20°C)
heatLockout
Disable 71.6°F (22°C)
htStageDelay
300 seconds
numHStages
0
Page 10 of 11
Document No. 588-150