Data Sheet for Product
Table Of Contents
Page 8 of 11 Document No. 588-894
Configuration Table
The following table lists all of the configuration properties (CPs) available with this
application. For more information on how to set these properties for a CV with Reheat
configuration, please consult the Predator VAV/CV Application Guide.
Configuration Properties - VAV/CV
Configuration Property Element Factory Value
actDisplay command
airTermType no_Fan
bypassTime 60 minutes
Pb 1.8°C 53.2°F)
Ti 300.0 seconds
clgDmdCtrB
Td 0.0 seconds
ductArea 1.0764 ft2 (0.1000 m2)
dynMinScope off
fanUnoccHtg modulate
fanWarmup on
TravelTime 90.0 sec
Reverse False
flowDmprMotr
SyncDirection close
SaturationLoad 110%
PrctDeadband 2%
flowDmprSat
TimeDelay 10 min
PercentOn 110.00%
flowFanRq
PercentOff 100.00%
flowUnoccHtg modulate
Enable TRUE
DmdAtMin 0.00%
flowVav
DmdAtMax 100.00%
flowWarmup off
PercentOn 3.00%
hCoilFanRq
PercentOff 0.00%
hCoilUnocc Cycle
hCoilWrmup Cycle
hStageCyc 10 minutes
DmdDeadband 5.00%
htgClgSwit
TmpDeadband 0.0°C (0.0°F)